Description : On-off and proportional control cabinet - DZR 45
This cabinet is for the relative humidity measurement and the proportional control of the humidifiers.
The IP65 sensor is protected against ammoniac and chlorine attacks for uses in aggressive environments. The sensor is insensible to condensation for perfect use until 100% relative humidity.
Build to control relative humidity wine chais, cheeses rooms, laboratories, industrials rooms, houses…where the very close control of the relative humidity is very important.
Technical Data : On-off and proportional control cabinet - DZR 45
General Characteristics | |
---|---|
Electrical supply | 230 V (Ph+N) |
Performances specifications RH : | |
Resolution | 0,5 % RH max 0,3 % H.R. typical |
Absolute accuracy | 0-10 % RH 2-4 % RH 10-90 % RH < 2 % RH 90-100 % RH 2-4 % RH |
Reponse time | 4 sec. |
Longterm stability | < 1 % RH /year |
Performances specifications Temperature : | |
Resolution | 0,04 °C max 0,01 °C typical |
Absolute accuracy | 0,5°C at 25°C |
Reponse time | 5 sec. |
Operating Limits : | |
Relative humidity (sensor) | 0 - 100 % |
Temperature (sensor) | -40 to +123°C |
Simplified navigation graphic display
Supplied with HR probe and temp. HS-91 with heating element
Integrated timer to set different setpoints depending on time of day.
Hygrometry and temperature display
Two outputs NO / NC
A 0-10 V output for humidification
A 0-10 V output for dehumidification.
Designed for two HS-91 probes (for high or low limit or 2 locals)
Indication of the status of the outputs 0-10 V and T.O.R. By LEDs
Alarm output HR or Temperature, high or low, by dry contact