Description : Low pressure hot water heated air curtain - C2000WR
Adjustable outlet grille for precise control over the direction of air.
Supplied with a remote switch unit allowing fan speeds.
Technical Data : Low pressure hot water heated air curtain - C2000WR
| General Characteristics | |
|---|---|
| Overall length | 2090 mm |
| Air flow length | 2000 mm |
| Max. mounting height | 2.3 m |
| Height | 206 mm |
| Depth | 353 mm |
| Grille dimensions | 2120 x 353mm |
| Motor power | 360 W |
| Noise level | 50/53/55 dB (A) |
| Fan speeds Nos. | 3 |
| Max. air velocity | 9 m/s |
| Air velocity 2 | 8 m/s |
| Air velocity 1 | 7 m/s |
| Max air volume | 2240 m³/h |
| Air volume 2 | 2250 m³/h |
| Air volume 1 | 1800 m³/h |
| Supply | 220/240 V 1N~ |
| Max input | 1.6 A |
| Weight | 37 kg |
| Mounting | Recessed, Horizontal |
| Color | White |
| Warrantly | 5 years |
| Low pressure hot water | |
| Heat output | 10000 kcal/h |
| Heat output | 12 kW |
| Flow rate | 17.4 L/min |
| Pressure Diff. | 13.40 kPa |
Noise level values are measured 3 m from the outlet grille.
Optional devices available on request:
• electronic remote switch unit with thermostatic control
• alternative coils
Youtube
LinkedIn