The adsorption dryer controls the relative humidity of unheated premises such as cold rooms or storage rooms for wood, iron, cardboard, textiles, seeds, sugar ... For industry, museums or defense for example.
Description : Double way adsorption dryer - C30-300-1,9
The adsorption dryer controls the relating humidity of the not heated places such cold rooms or stores of stocking of wood, iron, cardboard, textile industry, kernels, sugar …for industry, museums or defence for instance. The dryer also abolishes condensation in the cold surface of pipes, reservoirs, pumps, hoods of protection, building and electrical and electronic installations. . It protects the works of arts, the post offices of piloting (military installations, power stations, dockyard, planes, boats, satellites, etc).
And of course the dryer allows to adjust hygrometry during production and manufacture of hygroscopic products in pharmaceutical industry and in food industry between others.
Air process (air to be treated) crosses the wheel in permanent rotation; this one keeps the humidity contained in air. A flux of air heated by electrical resistance, says air of regeneration, is injected into the wheel in compared sense. This hot air evaporates the water contained in the wheel then is evacuated of the apparatus towards the outside. Each of both fluxes has his own fan.
The wheel is fabricated from 80 % minimum of Silicate, which is supported by a chemical resolution without solvent based on glass fibbers. In stage of regeneration, the temperature of the wheel is about 120-140°C.
Technical Data : Double way adsorption dryer - C30-300-1,9
General Characteristics | |
---|---|
Intensity | yes |
Hour counter | yes |
Manufacturer warrantly | 2 years |
Power rating | 2.9 kW |
Electrical supply | 400 V (3Ph) |
Frequency | 50 Hz |
Metal work | INOX |
Control | on / off |
Dehumidification at 20°C - 60% R.H. | 1.9 L/h |
Ambiance Heating Power | 40% of power supply |
CE Approval | Yes |
Dimensions and Weights : | |
Height | 771 mm |
Width | 554 mm |
Depth | 398 mm |
Weight | 53 kg |
Process air (air to be treated) : | |
Air flow | 300 m³/h |
Pressure | 200 Pa |
Inlet conditions | 0 to 40°C, 0 to 99% RH |
Air filter | oui |
Inlet | Diam. 200 mm |
Outlet | Diam. 200 mm |
Regeneration air : | |
Air flow | 85 m³/h |
Pressure | 150 Pa |
Inlet conditions | 0 to 40°C, 0 to 99% RH |
Air filter | oui |
Inlet | Diam. 100 mm |
Outlet | Diam. 100 mm |